Every major way to cool an AI data center — from water-hungry cooling towers to chips with coolant etched into the silicon — shown in 40 renderings, with what each method costs in water.
PROJECTNo-More-Water Cooling Brief
SHEETFOS216-NMW-002
SCOPE19 methods · 40 renders
DATE2026-09-25
The FixOurStreets216 Project
Neighborhoods First · #WeThePeople
OVERVIEW
How to read this deck
Cooling a data center is two jobs: capture the heat at the chip or rack, then reject it somewhere outside. Water can be used — or consumed — at either step.
Each method slide shows
NO WATER USEDSealed loop or no liquid at all; no evaporation
MINIMAL / BACKUPSmall makeup or treatment volumes only
SEASONAL WATEREvaporates water on hot days only
HIGH WATER USEEvaporation is the main cooling mechanism
SAVES WATERReplaces fresh water or reuses heat
Renderings are concept visuals generated for discussion. Equipment, labels and brands shown are illustrative, not specified products.
OVERVIEW
Eight families of cooling
PART IThe baselineEvaporative cooling towers
PART IIAir-side heat rejectionDry coolers, fan walls, air-cooled chillers
PART IIIChiller plantsCentrifugal chillers and rooftop CDUs
PART IVRack & chip coolingRear doors, in-row, direct-to-chip, warm water
PART VImmersionSingle-phase and two-phase tanks
PART VINext frontierIn-chip microfluidics
PART VIINatural heat sinksDeep lake water, geothermal
PART VIIIWater sourcing & heat reuseReclaimed water, rain, absorption, district heat
PART I
The Baseline
The evaporative cooling tower — the technology the industry is designing out of new AI capacity.
THE BASELINE
Evaporative cooling towers
RENDER 00 · Towers with vapor plumes; blowdown discharging to a drain
How it works
Warm condenser water is sprayed over fill media while fans pull air through. A portion evaporates, carrying heat away. Minerals left behind are flushed out as blowdown, and fresh makeup water replaces both losses.
WATERHIGH WATER USE
DENSITY / SCALEAny · air-cooled racks
MATURITYLegacy standard
Cleveland fit
Works well thermally, but a traditional evaporative facility uses roughly 18,000 gallons per MW per day (industry average WUE 1.8–1.9 L/kWh). This is the “before” picture for every other slide.
PART II
Air-Side Heat Rejection
Moving heat into outdoor air — with fans and coils instead of evaporation.
A sealed glycol or water loop runs through finned coils; fans push outdoor air across them — a car radiator at building scale. Nothing evaporates, so the only water is the initial fill.
WATERNO WATER USED
DENSITY / SCALECampus scale
MATURITYMainstream
Cleveland fit
Strong fit. Cool air most of the year means dry coolers can carry the load alone for most hours, especially with 40–45°C warm-water liquid cooling. Needs roof or yard area and fan-noise planning.
AIR-SIDE
Adiabatic hybrid dry cooler
RENDER 18 · V-bank dry cooler with wetted pre-cooling pads and spray header, summer
How it works
Runs dry most of the year. On the hottest hours, water wets pads on the air intake so incoming air is pre-cooled by evaporation, boosting capacity exactly when it's needed.
WATERSEASONAL WATER
DENSITY / SCALECampus scale
MATURITYMainstream
Cleveland fit
Good insurance for Cleveland's short summer peaks. Water use is a small fraction of a tower's and can come from reclaimed water or rain storage.
AIR-SIDE
Fan walls & evaporative air galleries
RENDER 20Concrete cooling gallery: fan arrays paired with wetted-media panelsRENDER 21Fan wall with filter/media banks feeding a data hallRENDER 22Deep mechanical well with media walls and fan arrays beside the building
What these are: air handlers that push outdoor air straight through the building. In cool weather they run as a pure air-side economizer — no chillers, no water. The brown evaporative media panels are wetted on warm days to cool the air, which consumes water. SEASONAL WATER Best for air-cooled halls; AI racks above ~50 kW still need liquid cooling at the rack.
AIR-SIDE
Air-cooled chillers in acoustic enclosures
RENDER 09Air-cooled chiller inside a concrete enclosure with ventilation fansRENDER 10Row of open-top concrete enclosures around chiller modulesRENDER 11Enclosures lined with mineral-wool acoustic panels and louvers
Closed loop, no evaporation. Air-cooled chillers reject heat through their own condenser fans, so they use no water — but compressors and fans are loud. Concrete walls with absorptive mineral-wool linings and acoustic louvers cut noise toward neighbors while leaving an open top for airflow. NO WATER USED Key for Cleveland sites next to homes.
PART III
Chiller Plants
Mechanical refrigeration for when outdoor air alone can't do the job.
CHILLER PLANTS
Centrifugal chiller plant
RENDER 04 · Mechanical room with water-cooled centrifugal chillers and color-coded headers
How it works
A centrifugal compressor drives refrigerant through an evaporator (making chilled water for the building) and a condenser (dumping heat to a condenser-water loop). The large machines are the most efficient chillers at multi-megawatt scale.
WATERSEASONAL WATER
DENSITY / SCALEMulti-MW plants
MATURITYMature
Cleveland fit
Water use depends on where condenser heat goes: to cooling towers it is high; to dry coolers or lake water it is near zero. Oil-free magnetic-bearing compressors cut maintenance.
CHILLER PLANTS
Inside the mechanical room
RENDER 08Water-cooled centrifugal chiller (CenTraVac-style) with labeled evaporator and condenser loopsRENDER 06Heat-pump-capable centrifugal chiller — can recover heat instead of wasting itRENDER 07Chiller row feeding a glass-walled data hall
Render 08's labels show the classic legacy set points: 42°F chilled-water supply / 52°F return and 85–95°F condenser water. Modern AI plants run far warmer supply water, which lets chillers sit idle for most of the year. A heat-pump chiller (render 06) can upgrade rejected heat to useful temperatures for district heating.
CHILLER PLANTS
Rooftop chillers + CDUs over the data hall
RENDER 03Cutaway: rooftop centrifugal chillers and CDUs piped straight down to liquid-cooled racksRENDER 13Rooftop chillers and a two-phase refrigerant distribution unit over the hallRENDER 02Night view of the same rooftop plant
Stacking the chiller plant on the roof shortens pipe runs to the racks below and frees ground area — a fit for vertical, multi-story data buildings. CDUs (coolant distribution units) separate the building loop from the sealed technology loop that touches the servers.
Render note: renders 01, 02, 03, 05 and 13 show evaporative towers or vapor plumes in the background. Crop or regenerate them (“no cooling towers, no steam”) before using them to illustrate a water-free design.
CHILLER PLANTS
Screening the rooftop plant
RENDER 01Rooftop chillers inside a tall parapet screen, nightRENDER 05Drone view: fully enclosed rooftop plants across a campus
High parapet walls and enclosures block the line of sight from the plant to nearby homes and reduce chiller noise at the property line — the same concern as the ground-level acoustic enclosures. Use with a sound study against Cleveland's noise limits.
PART IV
Rack & Chip Cooling
Bringing liquid closer to the heat — the move that makes water-free heat rejection possible.
RACK & CHIP
Rear-door heat exchangers
RENDER 30 · Hot aisle lined with finned coil doors on every rack
How it works
A water coil replaces the rack's back door. Server fans push hot exhaust through the coil, which pulls the heat into a sealed water loop before the air re-enters the room.
WATERNO WATER USED
DENSITY / SCALE~30–60 kW / rack
MATURITYMainstream
Cleveland fit
An easy retrofit for existing air-cooled halls in Cleveland's older buildings; not enough on its own for 100 kW+ AI racks.
RACK & CHIP
In-row heat exchanger retrofit
RENDER 26 · Liquid-cooling cabinet placed in an existing air-cooled aisle, hoses to GPU servers
How it works
A cabinet the size of a rack sits in the row and contains pumps plus a liquid-to-air heat exchanger. It feeds cold plates on nearby servers and dumps the heat into the room's existing air system — no new facility piping. AWS built its own version (the IRHX) for this purpose.
WATERNO WATER USED
DENSITY / SCALEA few AI racks per row
MATURITYEmerging
Cleveland fit
Lets existing local data centers host some liquid-cooled AI gear without a major mechanical rebuild.
RACK & CHIP
Direct-to-chip liquid cooling
RENDER 15 · 120 kW AI rack with manifolds, blue TCS supply and red TCS return headers
How it works
Cold plates sit directly on GPUs and CPUs. Coolant from the technology cooling system (TCS) loop flows through each plate, picking up 70–100% of the rack's heat, and returns to a CDU.
WATERNO WATER USED
DENSITY / SCALE100–200 kW / rack
MATURITYAI standard
Cleveland fit
The core technology for any Cleveland AI campus. Paired with dry coolers, it consumes no water.
RACK & CHIP
Cold plates, up close
RENDER 16Open AI server: cold plate over the processor with quick-disconnect coolant linesRENDER 17Rack-level two-phase system: vapor lines and manifolds serving every tray
Each server tray connects to the rack manifold with dripless quick-disconnects, so a tray can be pulled for service without draining the loop. Single-phase plates use a water-glycol mix; two-phase plates use a refrigerant that boils on the chip.
A low-pressure refrigerant is pumped to evaporator plates on each chip, where it boils and absorbs heat as it changes phase. Vapor travels to a condenser and returns as liquid. Accelsius is one company building this type of system.
WATERNO WATER USED
DENSITY / SCALE1.5–2 kW+ chips
MATURITYEarly deployment
Cleveland fit
Handles next-generation chips that exceed single-phase limits, with roughly one-fifth the coolant flow. Refrigerant choice and handling are the open questions.
RACK & CHIP
Chiller-free warm-water loop
RENDER 39 · Cutaway: liquid-cooled racks, CDU, orange hot risers to rooftop dry coolers, teal returns
How it works
Chips tolerate coolant as warm as 45°C (113°F) (NVIDIA's Rubin-generation spec). At that temperature, the return water is hot enough to dump straight into outdoor air through dry coolers — no chiller, no tower.
WATERNO WATER USED
DENSITY / SCALEFull campus
MATURITYAI standard (2026)
Cleveland fit
The best fit for Cleveland: outdoor air here is far below 45°C all year. This is the design to lead with.
Render note: Two labels in this render should be corrected before public use: the rack labels name a specific GPU product, and the floor piping is labeled “cold-water” — it should read “warm-water supply.”
PART V
Immersion
Submerging the servers themselves in a non-conductive fluid.
IMMERSION
Single-phase immersion
RENDER 34 · Glass-sided immersion tank with servers submerged, CDU alongside
How it works
Servers are placed vertically in a tank of dielectric fluid — an oil-like liquid that doesn't conduct electricity. A pump circulates the fluid through a heat exchanger that hands the heat to a facility water loop.
WATERNO WATER USED
DENSITY / SCALE100 kW+ / tank
MATURITYGrowing niche
Cleveland fit
No server fans and no water at the rack. Floors must carry heavy tanks, and service crews need fluid-handling procedures.
IMMERSION
Single-phase immersion, inside the tank
RENDER 33Cutaway: submerged servers, flow manifold, pump and plate heat exchangerRENDER 35GPU module and heat sink fully submerged in dielectric fluid
Fluid enters low through a manifold, rises across the hardware and exits to the heat exchanger. Vendors report PUE as low as ~1.03–1.08, compared with a 2024 industry average of 1.56 (Uptime Institute).
IMMERSION
Two-phase immersion
RENDER 36 · Sealed tank: fluid boiling directly off the processors
How it works
The fluid is engineered to boil at a low temperature. It boils right off the chips, the vapor rises to a condenser coil in the lid, and it drips back down as liquid — no pump needed inside the tank.
WATERNO WATER USED
DENSITY / SCALEVery high
MATURITYNiche
Cleveland fit
Excellent heat transfer, but many two-phase fluids are fluorinated (PFAS-related), which adds regulatory and handling risk.
IMMERSION
Two-phase immersion at hall scale
RENDER 38Rows of two-phase tanks with plate heat exchangers and chilled-water headersRENDER 37Night view of an immersion hall
At hall scale, tanks replace rows of racks. Condenser coils in each lid connect to a facility water loop, which can reject heat through dry coolers. Sealed lids limit fluid loss; vapor escaping during service is the main environmental concern.
PART VI
Next Frontier
Cooling channels etched into the silicon itself.
NEXT FRONTIER
In-chip microfluidic cooling
RENDER 27 · Macro: branching, leaf-vein coolant channels etched into the back of a chip
How it works
Instead of a cold plate sitting on top of the chip, tiny channels are etched into the silicon so coolant flows right where heat is made. In 2025 Microsoft and Swiss startup Corintis reported up to 3× better heat removal than cold plates and a 65% lower peak temperature rise, using AI-designed channel patterns.
WATERNO WATER USED
DENSITY / SCALENext-gen chips
MATURITYR&D
Cleveland fit
Lets chips run hotter coolant, which makes water-free dry cooling even easier. A future manufacturing and research opportunity.
NEXT FRONTIER
Microfluidics in the lab
RENDER 28 · Research server tray with coolant lines connected directly to each GPU package
How it works
Prototype trays connect coolant directly to each processor package with no cold plate in between. Engineers measure flow, pressure and chip temperature at the bench before the design moves to production racks.
WATERNO WATER USED
DENSITY / SCALEPrototype
MATURITYR&D
Cleveland fit
A natural fit for Cleveland's research institutions and advanced-manufacturing base.
PART VII
Natural Heat Sinks
Using the lake and the ground as the cold side of the system.
NATURAL HEAT SINKS
Deep lake water cooling
RENDER 12 · Lakefront intake with screened inlet, large pipe and pump station
How it works
Cold water is drawn from deep in a lake through a screened intake, passed through heat exchangers to cool a sealed building loop, and returned to the lake. Toronto's Enwave system draws Lake Ontario water from about 83 m deep at roughly 4°C.
WATERNO WATER USED
DENSITY / SCALEDistrict / campus
MATURITYProven (Toronto)
Cleveland fit
Lake Erie is much shallower — the central basin off Cleveland averages about 18–25 m — so summer bottom water is warmer than Toronto's. Nothing evaporates, but discharge of warmer water needs a thermal study and an Ohio EPA discharge permit.
NATURAL HEAT SINKS
Ground-source borehole field
RENDER 23 · Campus borehole field under construction: capped wells, drill rig, HDPE pipe coils
How it works
Closed loops of plastic pipe run down vertical boreholes, often a few hundred feet deep. Fluid in the sealed loop trades heat with ground that stays near 50–55°F year-round in Ohio.
WATERNO WATER USED
DENSITY / SCALESupplemental
MATURITYProven (buildings)
Cleveland fit
Data centers only reject heat, so the ground warms over time. Best as a supplement or for office and support spaces, not the full IT load.
PART VIII
Water Sourcing & Heat Reuse
Making water a backup input and turning waste heat into a product.
SOURCING & REUSE
Reclaimed-water treatment building
RENDER 32 · Campus treatment building with purple reclaimed-water piping and storage tank
How it works
Treated municipal wastewater is piped in (purple pipe is the U.S. convention for non-potable reclaimed water), polished on site, and stored for cooling makeup. AWS used reclaimed water at 26 sites in 2025 and has agreements covering 130 data centers.
WATERSAVES WATER
DENSITY / SCALECampus
MATURITYMainstream
Cleveland fit
NEORSD's treatment plants make treated effluent available near several east-side sites. It replaces drinking water for any makeup the cooling system needs.
Absorption chillers make chilled water from heat instead of electricity, using a lithium bromide and water cycle. On a campus with on-site generation, turbine exhaust drives the chillers. BROAD is one of the best-known makers of this equipment.
WATERMINIMAL / BACKUP
DENSITY / SCALECampus with on-site power
MATURITYMature
Cleveland fit
Turns on-site power plant waste heat into cooling. Absorption chillers reject more total heat than electric chillers, so the heat-rejection side must be designed for dry coolers to stay water-free.
SOURCING & REUSE
District heating to the neighborhood
RENDER 24 · Winter dusk: insulated pipe from the data center to apartments and a community greenhouse
How it works
Warm return water (roughly 45–55°C from liquid-cooled racks) is piped to nearby buildings, often boosted by heat pumps. Meta's data center in Odense, Denmark already supplies the local district heating network.
WATERSAVES WATER
DENSITY / SCALENeighborhood
MATURITYProven (Europe)
Cleveland fit
A direct community benefit: heat for homes, greenhouses and businesses near the campus instead of heat dumped into the air.
SUMMARY
All 19 methods at a glance
Method
Renders
Water consumed
Scale
Maturity
Evaporative tower
00
High
Any
Legacy
Dry cooler
19
None
Campus
Mainstream
Adiabatic hybrid
18
Peak hours
Campus
Mainstream
Fan wall / evap. gallery
20–22
Warm days
Air halls
Mainstream
Air-cooled chiller
09–11
None
Plant
Mature
Centrifugal chiller
04–08
Depends on heat rejection
Multi-MW
Mature
Rear-door HX
30
None
30–60 kW
Mainstream
In-row HX retrofit
26
None
Per row
Emerging
Direct-to-chip
15–17
None
100–200 kW
AI standard
Two-phase DLC
14
None
1.5–2 kW+ chips
Early
Warm-water loop
39
None
Campus
AI standard
Single-phase immersion
33–35
None
100 kW+
Growing
Two-phase immersion
36–38
None
Very high
Niche
Microfluidics
27–28
None
Next-gen
R&D
Deep lake water
12
Non-consumptive
District
Proven
Geothermal
23
None
Supplemental
Proven
Reclaimed water
31–32
Replaces potable
Campus
Mainstream
Rainwater
29
Replaces potable
Supplemental
Mainstream
Absorption + district heat
24–25
Reuses heat
Campus
Mature
SUMMARY
The water-free stack for Cleveland
CaptureDirect-to-chip at 40–45°C
→
MoveSealed loop through CDUs
→
RejectDry coolers; trim chillers on peak days
+
BackupReclaimed water, not drinking water
+
Give backHeat to homes and greenhouses
Zero evaporation, zero potable water for cooling, quiet enclosed plants — and heat returned to the neighborhood.