FOS216-NMW-002 · REV A · VISUAL BRIEFING

Cooling,
Rendered

Every major way to cool an AI data center — from water-hungry cooling towers to chips with coolant etched into the silicon — shown in 40 renderings, with what each method costs in water.

PROJECTNo-More-Water Cooling Brief
SHEETFOS216-NMW-002
SCOPE19 methods · 40 renders
DATE2026-09-25
The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
01 / 41
OVERVIEW

How to read this deck

Cooling a data center is two jobs: capture the heat at the chip or rack, then reject it somewhere outside. Water can be used — or consumed — at either step.

1 · CAPTUREair, cold plate,immersion, in-chip 2 · MOVECDU, chiller,heat exchanger 3 · REJECTtower, dry cooler,lake, ground, reuse where most water is lost

Each method slide shows

NO WATER USEDSealed loop or no liquid at all; no evaporation
MINIMAL / BACKUPSmall makeup or treatment volumes only
SEASONAL WATEREvaporates water on hot days only
HIGH WATER USEEvaporation is the main cooling mechanism
SAVES WATERReplaces fresh water or reuses heat

Renderings are concept visuals generated for discussion. Equipment, labels and brands shown are illustrative, not specified products.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
02 / 41
OVERVIEW

Eight families of cooling

PART IThe baselineEvaporative cooling towers
PART IIAir-side heat rejectionDry coolers, fan walls, air-cooled chillers
PART IIIChiller plantsCentrifugal chillers and rooftop CDUs
PART IVRack & chip coolingRear doors, in-row, direct-to-chip, warm water
PART VImmersionSingle-phase and two-phase tanks
PART VINext frontierIn-chip microfluidics
PART VIINatural heat sinksDeep lake water, geothermal
PART VIIIWater sourcing & heat reuseReclaimed water, rain, absorption, district heat
The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
03 / 41
PART I

The Baseline

The evaporative cooling tower — the technology the industry is designing out of new AI capacity.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
04 / 41
THE BASELINE

Evaporative cooling towers

RENDER 00 · Towers with vapor plumes; blowdown discharging to a drain

How it works

Warm condenser water is sprayed over fill media while fans pull air through. A portion evaporates, carrying heat away. Minerals left behind are flushed out as blowdown, and fresh makeup water replaces both losses.

WATERHIGH WATER USE
DENSITY / SCALEAny · air-cooled racks
MATURITYLegacy standard

Cleveland fit

Works well thermally, but a traditional evaporative facility uses roughly 18,000 gallons per MW per day (industry average WUE 1.8–1.9 L/kWh). This is the “before” picture for every other slide.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
05 / 41
PART II

Air-Side Heat Rejection

Moving heat into outdoor air — with fans and coils instead of evaporation.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
06 / 41
AIR-SIDE

Dry coolers

RENDER 19 · Rooftop dry-cooler array, Cleveland winter, Lake Erie beyond

How it works

A sealed glycol or water loop runs through finned coils; fans push outdoor air across them — a car radiator at building scale. Nothing evaporates, so the only water is the initial fill.

WATERNO WATER USED
DENSITY / SCALECampus scale
MATURITYMainstream

Cleveland fit

Strong fit. Cool air most of the year means dry coolers can carry the load alone for most hours, especially with 40–45°C warm-water liquid cooling. Needs roof or yard area and fan-noise planning.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
07 / 41
AIR-SIDE

Adiabatic hybrid dry cooler

RENDER 18 · V-bank dry cooler with wetted pre-cooling pads and spray header, summer

How it works

Runs dry most of the year. On the hottest hours, water wets pads on the air intake so incoming air is pre-cooled by evaporation, boosting capacity exactly when it's needed.

WATERSEASONAL WATER
DENSITY / SCALECampus scale
MATURITYMainstream

Cleveland fit

Good insurance for Cleveland's short summer peaks. Water use is a small fraction of a tower's and can come from reclaimed water or rain storage.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
08 / 41
AIR-SIDE

Fan walls & evaporative air galleries

RENDER 20Concrete cooling gallery: fan arrays paired with wetted-media panels
RENDER 21Fan wall with filter/media banks feeding a data hall
RENDER 22Deep mechanical well with media walls and fan arrays beside the building
What these are: air handlers that push outdoor air straight through the building. In cool weather they run as a pure air-side economizer — no chillers, no water. The brown evaporative media panels are wetted on warm days to cool the air, which consumes water. SEASONAL WATER Best for air-cooled halls; AI racks above ~50 kW still need liquid cooling at the rack.
The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
09 / 41
AIR-SIDE

Air-cooled chillers in acoustic enclosures

RENDER 09Air-cooled chiller inside a concrete enclosure with ventilation fans
RENDER 10Row of open-top concrete enclosures around chiller modules
RENDER 11Enclosures lined with mineral-wool acoustic panels and louvers
Closed loop, no evaporation. Air-cooled chillers reject heat through their own condenser fans, so they use no water — but compressors and fans are loud. Concrete walls with absorptive mineral-wool linings and acoustic louvers cut noise toward neighbors while leaving an open top for airflow. NO WATER USED Key for Cleveland sites next to homes.
The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
10 / 41
PART III

Chiller Plants

Mechanical refrigeration for when outdoor air alone can't do the job.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
11 / 41
CHILLER PLANTS

Centrifugal chiller plant

RENDER 04 · Mechanical room with water-cooled centrifugal chillers and color-coded headers

How it works

A centrifugal compressor drives refrigerant through an evaporator (making chilled water for the building) and a condenser (dumping heat to a condenser-water loop). The large machines are the most efficient chillers at multi-megawatt scale.

WATERSEASONAL WATER
DENSITY / SCALEMulti-MW plants
MATURITYMature

Cleveland fit

Water use depends on where condenser heat goes: to cooling towers it is high; to dry coolers or lake water it is near zero. Oil-free magnetic-bearing compressors cut maintenance.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
12 / 41
CHILLER PLANTS

Inside the mechanical room

RENDER 08Water-cooled centrifugal chiller (CenTraVac-style) with labeled evaporator and condenser loops
RENDER 06Heat-pump-capable centrifugal chiller — can recover heat instead of wasting it
RENDER 07Chiller row feeding a glass-walled data hall
Render 08's labels show the classic legacy set points: 42°F chilled-water supply / 52°F return and 85–95°F condenser water. Modern AI plants run far warmer supply water, which lets chillers sit idle for most of the year. A heat-pump chiller (render 06) can upgrade rejected heat to useful temperatures for district heating.
The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
13 / 41
CHILLER PLANTS

Rooftop chillers + CDUs over the data hall

RENDER 03Cutaway: rooftop centrifugal chillers and CDUs piped straight down to liquid-cooled racks
RENDER 13Rooftop chillers and a two-phase refrigerant distribution unit over the hall
RENDER 02Night view of the same rooftop plant
Stacking the chiller plant on the roof shortens pipe runs to the racks below and frees ground area — a fit for vertical, multi-story data buildings. CDUs (coolant distribution units) separate the building loop from the sealed technology loop that touches the servers.
Render note: renders 01, 02, 03, 05 and 13 show evaporative towers or vapor plumes in the background. Crop or regenerate them (“no cooling towers, no steam”) before using them to illustrate a water-free design.
The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
14 / 41
CHILLER PLANTS

Screening the rooftop plant

RENDER 01Rooftop chillers inside a tall parapet screen, night
RENDER 05Drone view: fully enclosed rooftop plants across a campus
High parapet walls and enclosures block the line of sight from the plant to nearby homes and reduce chiller noise at the property line — the same concern as the ground-level acoustic enclosures. Use with a sound study against Cleveland's noise limits.
The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
15 / 41
PART IV

Rack & Chip Cooling

Bringing liquid closer to the heat — the move that makes water-free heat rejection possible.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
16 / 41
RACK & CHIP

Rear-door heat exchangers

RENDER 30 · Hot aisle lined with finned coil doors on every rack

How it works

A water coil replaces the rack's back door. Server fans push hot exhaust through the coil, which pulls the heat into a sealed water loop before the air re-enters the room.

WATERNO WATER USED
DENSITY / SCALE~30–60 kW / rack
MATURITYMainstream

Cleveland fit

An easy retrofit for existing air-cooled halls in Cleveland's older buildings; not enough on its own for 100 kW+ AI racks.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
17 / 41
RACK & CHIP

In-row heat exchanger retrofit

RENDER 26 · Liquid-cooling cabinet placed in an existing air-cooled aisle, hoses to GPU servers

How it works

A cabinet the size of a rack sits in the row and contains pumps plus a liquid-to-air heat exchanger. It feeds cold plates on nearby servers and dumps the heat into the room's existing air system — no new facility piping. AWS built its own version (the IRHX) for this purpose.

WATERNO WATER USED
DENSITY / SCALEA few AI racks per row
MATURITYEmerging

Cleveland fit

Lets existing local data centers host some liquid-cooled AI gear without a major mechanical rebuild.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
18 / 41
RACK & CHIP

Direct-to-chip liquid cooling

RENDER 15 · 120 kW AI rack with manifolds, blue TCS supply and red TCS return headers

How it works

Cold plates sit directly on GPUs and CPUs. Coolant from the technology cooling system (TCS) loop flows through each plate, picking up 70–100% of the rack's heat, and returns to a CDU.

WATERNO WATER USED
DENSITY / SCALE100–200 kW / rack
MATURITYAI standard

Cleveland fit

The core technology for any Cleveland AI campus. Paired with dry coolers, it consumes no water.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
19 / 41
RACK & CHIP

Cold plates, up close

RENDER 16Open AI server: cold plate over the processor with quick-disconnect coolant lines
RENDER 17Rack-level two-phase system: vapor lines and manifolds serving every tray
Each server tray connects to the rack manifold with dripless quick-disconnects, so a tray can be pulled for service without draining the loop. Single-phase plates use a water-glycol mix; two-phase plates use a refrigerant that boils on the chip.
The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
20 / 41
RACK & CHIP

Two-phase direct-to-chip

RENDER 14 · Engineering cutaway: refrigerant distribution, on-chip evaporators, vapor headers, condenser

How it works

A low-pressure refrigerant is pumped to evaporator plates on each chip, where it boils and absorbs heat as it changes phase. Vapor travels to a condenser and returns as liquid. Accelsius is one company building this type of system.

WATERNO WATER USED
DENSITY / SCALE1.5–2 kW+ chips
MATURITYEarly deployment

Cleveland fit

Handles next-generation chips that exceed single-phase limits, with roughly one-fifth the coolant flow. Refrigerant choice and handling are the open questions.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
21 / 41
RACK & CHIP

Chiller-free warm-water loop

RENDER 39 · Cutaway: liquid-cooled racks, CDU, orange hot risers to rooftop dry coolers, teal returns

How it works

Chips tolerate coolant as warm as 45°C (113°F) (NVIDIA's Rubin-generation spec). At that temperature, the return water is hot enough to dump straight into outdoor air through dry coolers — no chiller, no tower.

WATERNO WATER USED
DENSITY / SCALEFull campus
MATURITYAI standard (2026)

Cleveland fit

The best fit for Cleveland: outdoor air here is far below 45°C all year. This is the design to lead with.

Render note: Two labels in this render should be corrected before public use: the rack labels name a specific GPU product, and the floor piping is labeled “cold-water” — it should read “warm-water supply.”
The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
22 / 41
PART V

Immersion

Submerging the servers themselves in a non-conductive fluid.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
23 / 41
IMMERSION

Single-phase immersion

RENDER 34 · Glass-sided immersion tank with servers submerged, CDU alongside

How it works

Servers are placed vertically in a tank of dielectric fluid — an oil-like liquid that doesn't conduct electricity. A pump circulates the fluid through a heat exchanger that hands the heat to a facility water loop.

WATERNO WATER USED
DENSITY / SCALE100 kW+ / tank
MATURITYGrowing niche

Cleveland fit

No server fans and no water at the rack. Floors must carry heavy tanks, and service crews need fluid-handling procedures.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
24 / 41
IMMERSION

Single-phase immersion, inside the tank

RENDER 33Cutaway: submerged servers, flow manifold, pump and plate heat exchanger
RENDER 35GPU module and heat sink fully submerged in dielectric fluid
Fluid enters low through a manifold, rises across the hardware and exits to the heat exchanger. Vendors report PUE as low as ~1.03–1.08, compared with a 2024 industry average of 1.56 (Uptime Institute).
The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
25 / 41
IMMERSION

Two-phase immersion

RENDER 36 · Sealed tank: fluid boiling directly off the processors

How it works

The fluid is engineered to boil at a low temperature. It boils right off the chips, the vapor rises to a condenser coil in the lid, and it drips back down as liquid — no pump needed inside the tank.

WATERNO WATER USED
DENSITY / SCALEVery high
MATURITYNiche

Cleveland fit

Excellent heat transfer, but many two-phase fluids are fluorinated (PFAS-related), which adds regulatory and handling risk.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
26 / 41
IMMERSION

Two-phase immersion at hall scale

RENDER 38Rows of two-phase tanks with plate heat exchangers and chilled-water headers
RENDER 37Night view of an immersion hall
At hall scale, tanks replace rows of racks. Condenser coils in each lid connect to a facility water loop, which can reject heat through dry coolers. Sealed lids limit fluid loss; vapor escaping during service is the main environmental concern.
The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
27 / 41
PART VI

Next Frontier

Cooling channels etched into the silicon itself.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
28 / 41
NEXT FRONTIER

In-chip microfluidic cooling

RENDER 27 · Macro: branching, leaf-vein coolant channels etched into the back of a chip

How it works

Instead of a cold plate sitting on top of the chip, tiny channels are etched into the silicon so coolant flows right where heat is made. In 2025 Microsoft and Swiss startup Corintis reported up to 3× better heat removal than cold plates and a 65% lower peak temperature rise, using AI-designed channel patterns.

WATERNO WATER USED
DENSITY / SCALENext-gen chips
MATURITYR&D

Cleveland fit

Lets chips run hotter coolant, which makes water-free dry cooling even easier. A future manufacturing and research opportunity.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
29 / 41
NEXT FRONTIER

Microfluidics in the lab

RENDER 28 · Research server tray with coolant lines connected directly to each GPU package

How it works

Prototype trays connect coolant directly to each processor package with no cold plate in between. Engineers measure flow, pressure and chip temperature at the bench before the design moves to production racks.

WATERNO WATER USED
DENSITY / SCALEPrototype
MATURITYR&D

Cleveland fit

A natural fit for Cleveland's research institutions and advanced-manufacturing base.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
30 / 41
PART VII

Natural Heat Sinks

Using the lake and the ground as the cold side of the system.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
31 / 41
NATURAL HEAT SINKS

Deep lake water cooling

RENDER 12 · Lakefront intake with screened inlet, large pipe and pump station

How it works

Cold water is drawn from deep in a lake through a screened intake, passed through heat exchangers to cool a sealed building loop, and returned to the lake. Toronto's Enwave system draws Lake Ontario water from about 83 m deep at roughly 4°C.

WATERNO WATER USED
DENSITY / SCALEDistrict / campus
MATURITYProven (Toronto)

Cleveland fit

Lake Erie is much shallower — the central basin off Cleveland averages about 18–25 m — so summer bottom water is warmer than Toronto's. Nothing evaporates, but discharge of warmer water needs a thermal study and an Ohio EPA discharge permit.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
32 / 41
NATURAL HEAT SINKS

Ground-source borehole field

RENDER 23 · Campus borehole field under construction: capped wells, drill rig, HDPE pipe coils

How it works

Closed loops of plastic pipe run down vertical boreholes, often a few hundred feet deep. Fluid in the sealed loop trades heat with ground that stays near 50–55°F year-round in Ohio.

WATERNO WATER USED
DENSITY / SCALESupplemental
MATURITYProven (buildings)

Cleveland fit

Data centers only reject heat, so the ground warms over time. Best as a supplement or for office and support spaces, not the full IT load.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
33 / 41
PART VIII

Water Sourcing & Heat Reuse

Making water a backup input and turning waste heat into a product.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
34 / 41
SOURCING & REUSE

Reclaimed-water treatment building

RENDER 32 · Campus treatment building with purple reclaimed-water piping and storage tank

How it works

Treated municipal wastewater is piped in (purple pipe is the U.S. convention for non-potable reclaimed water), polished on site, and stored for cooling makeup. AWS used reclaimed water at 26 sites in 2025 and has agreements covering 130 data centers.

WATERSAVES WATER
DENSITY / SCALECampus
MATURITYMainstream

Cleveland fit

NEORSD's treatment plants make treated effluent available near several east-side sites. It replaces drinking water for any makeup the cooling system needs.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
35 / 41
SOURCING & REUSE

High-recovery treatment room

RENDER 31 · Reverse-osmosis pressure vessels, pumps and purple RO-water piping

How it works

Reverse-osmosis and filtration trains remove dissolved minerals so water can be reused many more times before discharge, shrinking blowdown volume.

WATERMINIMAL / BACKUP
DENSITY / SCALECampus
MATURITYMainstream

Cleveland fit

Pairs with reclaimed water so the campus draws no potable water and discharges less to the sewer.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
36 / 41
SOURCING & REUSE

Rainwater harvesting

RENDER 29 · Roof drains feeding a row of green storage tanks, light rain

How it works

Roof runoff is collected, filtered and stored for makeup water or site irrigation. AWS reports rainwater collection at 14 data centers.

WATERSAVES WATER
DENSITY / SCALESupplemental
MATURITYMainstream

Cleveland fit

Cleveland gets about 40 inches of precipitation a year. Harvesting also reduces stormwater runoff to the combined sewer.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
37 / 41
SOURCING & REUSE

Waste-heat absorption chillers

RENDER 25 · Energy center: gas-turbine exhaust duct feeding lithium bromide absorption chillers

How it works

Absorption chillers make chilled water from heat instead of electricity, using a lithium bromide and water cycle. On a campus with on-site generation, turbine exhaust drives the chillers. BROAD is one of the best-known makers of this equipment.

WATERMINIMAL / BACKUP
DENSITY / SCALECampus with on-site power
MATURITYMature

Cleveland fit

Turns on-site power plant waste heat into cooling. Absorption chillers reject more total heat than electric chillers, so the heat-rejection side must be designed for dry coolers to stay water-free.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
38 / 41
SOURCING & REUSE

District heating to the neighborhood

RENDER 24 · Winter dusk: insulated pipe from the data center to apartments and a community greenhouse

How it works

Warm return water (roughly 45–55°C from liquid-cooled racks) is piped to nearby buildings, often boosted by heat pumps. Meta's data center in Odense, Denmark already supplies the local district heating network.

WATERSAVES WATER
DENSITY / SCALENeighborhood
MATURITYProven (Europe)

Cleveland fit

A direct community benefit: heat for homes, greenhouses and businesses near the campus instead of heat dumped into the air.

The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
39 / 41
SUMMARY

All 19 methods at a glance

MethodRendersWater consumedScaleMaturity
Evaporative tower00HighAnyLegacy
Dry cooler19NoneCampusMainstream
Adiabatic hybrid18Peak hoursCampusMainstream
Fan wall / evap. gallery20–22Warm daysAir hallsMainstream
Air-cooled chiller09–11NonePlantMature
Centrifugal chiller04–08Depends on heat rejectionMulti-MWMature
Rear-door HX30None30–60 kWMainstream
In-row HX retrofit26NonePer rowEmerging
Direct-to-chip15–17None100–200 kWAI standard
Two-phase DLC14None1.5–2 kW+ chipsEarly
Warm-water loop39NoneCampusAI standard
Single-phase immersion33–35None100 kW+Growing
Two-phase immersion36–38NoneVery highNiche
Microfluidics27–28NoneNext-genR&D
Deep lake water12Non-consumptiveDistrictProven
Geothermal23NoneSupplementalProven
Reclaimed water31–32Replaces potableCampusMainstream
Rainwater29Replaces potableSupplementalMainstream
Absorption + district heat24–25Reuses heatCampusMature
The FixOurStreets216 Project
FOS216-NMW-002 · REV A · 2026-09-25
40 / 41
SUMMARY

The water-free stack for Cleveland

CaptureDirect-to-chip at 40–45°C
→
MoveSealed loop through CDUs
→
RejectDry coolers; trim chillers on peak days
+
BackupReclaimed water, not drinking water
+
Give backHeat to homes and greenhouses

Zero evaporation, zero potable water for cooling, quiet enclosed plants — and heat returned to the neighborhood.