Water Is
History
How hyperscalers are engineering evaporation out of data center cooling — and the methods replacing the cooling tower.
How hyperscalers are engineering evaporation out of data center cooling — and the methods replacing the cooling tower.
The new default for AI builds: closed-loop liquid-to-chip cooling + dry coolers, with reclaimed water only as backup makeup.
AI racks run 100–200 kW. NVIDIA Blackwell-class GPUs draw ~1,000–1,200 W each; Rubin racks are 100% liquid cooled with no fans. Air cannot carry that heat, and evaporative towers add cost without solving it at the chip.
Communities from Arizona to Georgia to Wisconsin now ask how many gallons a campus will take before zoning votes. Water has become a permitting issue, not just an operating cost.
The EU Energy Efficiency Directive requires data centers to report water use. Google (June 2026) published proposed industry water standards. WUE now sits beside PUE in procurement and ESG reporting.
Chips tolerate 45°C coolant. Heat at that temperature can be dumped to outdoor air nearly year-round — no tower, no chiller, and a smaller electric bill.
Bar height = heat density each method can handle. Everything right of the tower can run with a sealed water loop; the difference is how close the liquid gets to the silicon.
Refrigerant boils inside the cold plate, absorbing heat as it changes phase.
Coolant channels etched into the back of the silicon itself — no cold plate in between.
Treated municipal wastewater replaces potable makeup. AWS: 26 sites on reclaimed water in 2025, agreements with 13 utilities covering 130 data centers. EPA's Water Reuse Action Plan supports industrial cooling reuse.
High-recovery treatment (e.g., Gradiant-type systems) cycles water many more times and shrinks blowdown. Rainwater harvesting covers makeup at some sites (AWS: 14 data centers).
45–55°C return water is useful heat: district heating, greenhouses, and industrial process loads. Where on-site generation exists, turbine exhaust can drive absorption chillers — cooling from waste heat, not electricity.
The trend: water becomes a backup input sourced from wastewater, and heat becomes a product instead of a waste stream.
| Method | On-site water | Rack density | Energy effect | Maturity | Main tradeoff |
|---|---|---|---|---|---|
| Evaporative tower | High · WUE 1.8+ | Air racks | Lowest energy in hot, dry climates | Legacy | Water, blowdown, permitting |
| Adiabatic hybrid | Peak hours only | Air racks | Slightly higher | Mainstream | Still some water on hot days |
| Dry cooler + closed loop | ~0 consumed | Air / RDHx | + fan & chiller energy | Mainstream | Footprint, noise |
| Direct-to-chip (warm) | ~0 consumed | 100–200 kW | Chillers mostly off | AI standard | Plumbing to every server |
| Immersion | None at rack | 100+ kW | PUE as low as ~1.03 (vendor) | Niche / growing | Fluids, weight, serviceability |
| Two-phase cold plate | ~0 consumed | 1.5–2 kW+ chips | Low pump energy | 2026–27 rollout | Refrigerant choice |
| Microfluidic | ~0 consumed | Next-gen | 3× heat removal | R&D | Chip-level manufacturing |
The colder the air, the more hours a dry cooler handles alone. That makes the Great Lakes region one of the lowest-penalty places in the U.S. to build water-free AI capacity.
Cold winters and moderate summers keep outdoor air below 45°C coolant temperatures year-round, so warm-water DLC can reject heat with dry coolers alone for most hours.
Lake Erie proximity plus NEORSD treated effluent as a reclaimed-water backup for makeup, flushing and emergencies — no potable draw, no blowdown.
Prefabricated mechanical floors, CDU skids, risers and roof dry-cooler platforms are manufacturable locally — fits the HOLON / B-Core factory strategy.
Result: zero evaporative loss and zero potable-water demand for cooling.
| Component | Cost / MW | Notes |
|---|---|---|
| Direct-to-chip liquid cooling | $1.3M–$1.9M / MW | |
| DLC cold plates + manifolds | $0.9M–$1.3M | AI racks (100–200 kW) |
| Pumping stations | $0.25M–$0.35M | N+1 redundancy |
| Heat-exchanger integration | $0.15M–$0.25M | Floor-level HX |
| Chiller plant (magnetic-bearing) | $1.2M–$1.8M / MW | |
| Magnetic-bearing chillers | $0.8M–$1.2M | Oil-free |
| Chiller electrical + switchgear | $0.25M–$0.35M | Medium-voltage |
| Chiller plant piping | $0.15M–$0.25M | Vertical risers |
| Dry coolers | $0.6M–$0.9M / MW | |
| Dry coolers | $0.45M–$0.65M | Cleveland climate advantage |
| Roof structural integration | $0.10M–$0.18M | Vertical tower design |
| Controls + VFD fans | $0.05M–$0.10M | AI-optimized |
| Water reuse & treatment | $0.20M–$0.31M / MW | |
| High-recovery treatment | $0.12M–$0.18M | Gradiant-type |
| Reclaimed-water interface | $0.05M–$0.08M | NEORSD tie-in |
| Storage + buffer tanks | $0.03M–$0.05M | Emergency makeup |
| Modular mechanical floors | $0.50M–$0.78M / MW | |
| Prefabricated mechanical floors | $0.35M–$0.55M | DLC manifolds + pumps |
| Vertical risers | $0.10M–$0.15M | Chilled water + power |
| Roof platforms | $0.05M–$0.08M | Dry-cooler mounting |
| Total cooling CAPEX | $3.8M–$5.7M per MW | |
100 MW: $380M–$570M · 300 MW: $1.14B–$1.71B. Planning-level ranges from the project cost model, not vendor quotes. Chiller line assumes a full plant; trim-only chillers with warm-water DLC would lower it.
| Cooling OPEX line | Per MW IT / yr | Basis |
|---|---|---|
| Cooling electricity | $68k–$102k | PUE overhead 0.12–0.18 × 8,760 MWh × $65/MWh |
| Water (reclaimed makeup + treatment) | $13k–$25k | No evaporative loss |
| Maintenance (DLC, chillers, dry coolers) | $45k–$78k | Pumps, manifolds, HX, fans |
| Total cooling OPEX | $126k–$205k per MW per year | |
Every 0.01 of PUE overhead on a 100 MW campus is about $570k a year at $65/MWh. Warm-water DLC keeps chillers off most of the year, which is where Cleveland's climate pays off.
Assumes full IT load, 8,760 hours, $0.065/kWh industrial rate. Water and maintenance ranges are project planning estimates.
| Year-1 line item | $M / yr | Basis |
|---|---|---|
| Revenue | ||
| AI hosting (wholesale) | 246.0 | 100 MW × $205 / kW-month |
| Operating cost | ||
| Electricity, IT + cooling | 65.5 | 100 MW × PUE 1.15 × 8,760 h × $0.065 |
| Cooling water + maintenance | 8.1 | Midpoint $80.5k / MW (energy already in PUE) |
| Staffing + operations | 15.0 | Midpoint |
| Non-cooling maintenance | 10.0 | UPS, switchgear, building |
| Total OPEX | 98.5 | |
| EBITDA (year 1) | $147.5M · 60% margin | |
CAPEX $1.12B = cooling $475M + building $320M + power $280M + land/site $45M. Escalation: revenue 1.5%, electricity 2.1%, other costs 2.0% per year. Year-10 EBITDA $162.8M; terminal value 10× EBITDA.
Income and property taxes · GPU / equipment refresh · lease-up ramp and vacancy · insurance. Each lowers these returns; add them before investor use. Revenue rate and power price are planning assumptions, not quotes.
Company figures are self-reported. Cost ranges are planning-level estimates for discussion, not vendor quotes. FOR DISCUSSION — NOT FOR CONSTRUCTION.