FOS216-NMW-001 · REV B · BRIEFING DECK

Water Is
History

How hyperscalers are engineering evaporation out of data center cooling — and the methods replacing the cooling tower.

PROJECTNo-More-Water Cooling Brief
SHEETFOS216-NMW-001
SCOPEHyperscale / AI
DATE2026-09-25
FOS216 logo
The FixOurStreets216 Project
Neighborhoods First · #WeThePeople
The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
01 / 21
EXECUTIVE SUMMARY

The bottom line

Hyperscalers are not abandoning water. They are eliminating water loss — sealing it in a loop, filling it once, and rejecting heat to the air.
~0
L/kWh on-site water target for new AI designs (Microsoft, Meta, NVIDIA DSX)
45°C
Coolant supply for NVIDIA Rubin-class racks — warm enough to skip chillers in most climates
17B
Gallons consumed directly by U.S. data centers in 2023 (LBNL) — triple 2014
2030
Water-positive deadline set by Microsoft, Google, Meta and AWS

The new default for AI builds: closed-loop liquid-to-chip cooling + dry coolers, with reclaimed water only as backup makeup.

The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
02 / 21
THE PROBLEM

How the old model drinks water

DATA HALL CHILLERcondenser water COOLINGTOWER EVAPORATED — GONE fresh makeup water blowdown
  • Evaporation is the cooling. Towers reject heat by boiling off water; most of what is withdrawn never comes back.
  • ~18,000 gal / MW / day for a traditional evaporative facility — roughly 2.6–6.6 million gallons per MW per year depending on climate and design.
  • Industry average WUE: 1.8–1.9 L/kWh, versus near zero for air-cooled or sealed-loop sites.
  • U.S. scale: 5.6B gal (2014) → 17B gal (2023). Hyperscale alone could reach 16–33B gal/yr by 2028 (LBNL).
  • Blowdown carries concentrated minerals and treatment chemicals to the sewer.
The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
03 / 21
FOUR DRIVERS

Why the shift is happening now

▲

Heat density

AI racks run 100–200 kW. NVIDIA Blackwell-class GPUs draw ~1,000–1,200 W each; Rubin racks are 100% liquid cooled with no fans. Air cannot carry that heat, and evaporative towers add cost without solving it at the chip.

●

Water stress & community pushback

Communities from Arizona to Georgia to Wisconsin now ask how many gallons a campus will take before zoning votes. Water has become a permitting issue, not just an operating cost.

■

Disclosure & regulation

The EU Energy Efficiency Directive requires data centers to report water use. Google (June 2026) published proposed industry water standards. WUE now sits beside PUE in procurement and ESG reporting.

◆

Warm water changes the math

Chips tolerate 45°C coolant. Heat at that temperature can be dumped to outdoor air nearly year-round — no tower, no chiller, and a smaller electric bill.

The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
04 / 21
THE METRIC

Measuring it: Water Usage Effectiveness

LITERS OF ON-SITE WATER PER kWh OF IT ENERGY Industry average 1.8–1.9 Microsoft 2021 0.49 Microsoft FY2024 0.30 AWS 2025 0.12 Sealed-loop AI design ≈ 0 (fill once)
WUE = site water (L) ÷ IT energy (kWh)
  • The water counterpart to PUE. Lower is better; zero means no ongoing on-site consumption.
  • AWS reached 0.12 L/kWh in 2025 — down 52% from 2021 — alongside a PUE of 1.14.
  • Microsoft improved 39% from 2021 to FY2024 and says its new designs target near-zero.
  • WUE counts on-site water only. Water used at power plants (“source” or indirect water) is extra — one reason on-site generation choices matter.
The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
05 / 21
INDUSTRY MOVES

What the hyperscalers are actually doing

Microsoft

  • All new designs since Aug 2024 use zero-water-for-cooling closed loops
  • Avoids 125M+ liters / yr per data center
  • Pilots: Phoenix, AZ and Mt. Pleasant, WI (2026)
  • Fairwater AI campus: loop filled once at construction
  • In-chip microfluidic cooling in R&D

AWS

  • Custom In-Row Heat Exchanger (IRHX) brings liquid-to-chip into existing halls
  • WUE 0.12 L/kWh (2025)
  • Reclaimed water at 130 data centers via 13 utilities — ~6B liters/yr fresh water saved
  • On-site treatment at 31 sites

Google

  • ~2/3 of fleet still evaporative; air cooling in water-stressed regions
  • Published proposed industry water standards (June 2026)
  • Candid on the tradeoff: air cooling uses ~10% more energy on average
  • Water-positive target: 2030

Meta

  • Next-gen AI design: closed-loop liquid cooling + dry coolers
  • Outside-air cooling most of the year where climate allows
  • Water positive by 2030: restore 200% in high-stress, 100% in medium-stress regions

NVIDIA

  • Rubin racks: 45°C coolant in, ~55°C out
  • DSX reference design: chiller-less dry cooling in suitable climates
  • From ~2.6M gal / MW / yr to near zero
  • 50 MW site: $4M+ / yr cooling energy + water savings
The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
06 / 21
THE LANDSCAPE

The cooling spectrum: from evaporation to the chip

HIGH WATER CONSUMPTION NEAR-ZERO WATER · HIGHEST DENSITY Evaporative tower WUE 1.8+ air racks Adiabatic hybrid wet only on peaks air racks Dry cooler + loop ~0 consumed air / RDHx Rear-door HX ~0 consumed 30–60 kW Direct-to-chip ~0 consumed 100–200 kW Immersion ~0 consumed 100+ kW Microfluidic / 2‑phase ~0 consumed 1.5–2 kW+ chips

Bar height = heat density each method can handle. Everything right of the tower can run with a sealed water loop; the difference is how close the liquid gets to the silicon.

The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
07 / 21
HEAT REJECTION

Method 1 — Dry coolers & adiabatic hybrids

WARM AIR OUT — NO VAPOR finned coil · sealed glycol / water loop hot supply from building cooled return
  • How it works: fans push outdoor air across a finned coil — a car radiator at building scale. Water stays inside the pipe.
  • Adiabatic assist: on the hottest hours, pads pre-cool inlet air with a small spray. Water is used only when needed, a fraction of a tower's annual draw.
  • The limit: a dry cooler can only get the loop a few degrees above outdoor dry-bulb. With 45°C chip coolant, that ceiling rarely matters.
  • Tradeoff: more fan energy and more roof or yard area than a tower; noise must be managed.
The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
08 / 21
THE MICROSOFT MODEL

Method 2 — Closed-loop chilled water, filled once

  • Sealed loop: water is charged at construction and circulates between servers and chillers indefinitely. Small makeup volumes cover leaks, service and flushing.
  • Economizing chillers: high-efficiency air-cooled chillers (often oil-free, magnetic-bearing compressors) run only when outdoor air can't do the job alone.
  • Elevated water temperatures widen the free-cooling window and keep the energy penalty “nominal,” per Microsoft.
  • Result: 125M+ liters avoided per data center per year; Fairwater's annual draw compared to a single restaurant (company claim).
SERVERScold plates / CDU AIR-COOLEDCHILLEReconomizer mode warm returncool supply FILL ONCE heat → outdoor air
The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
09 / 21
THE KEY UNLOCK

Method 3 — Direct-to-chip liquid cooling (warm water)

AI RACK100–200 kW CDUcoolant distribution DRY COOLERoutdoor air 55°C45°C ~50°C~40°C technology loop (sealed)facility loop (sealed) NO TOWER · NO CHILLER ON MOST DAYS · NO EVAPORATION
  • Cold plates sit directly on GPUs and CPUs; liquid carries ~70–100% of rack heat, air handles the rest.
  • Warm-water design: ASHRAE liquid classes W32–W45 and NVIDIA's 45°C spec mean the return is hot enough to dump to outdoor air almost all year.
  • Raising plant water temperature 1°C cuts cooling cost ~4% (NVIDIA).
  • AWS IRHX retrofits this into existing air-cooled halls without new construction.
  • Single-phase cold plates top out near 1.5–2 kW per chip — the next slides show what comes after.
The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
10 / 21
SUBMERGE THE SERVER

Method 4 — Immersion cooling

DIELECTRIC FLUID TANK HEATEXCHANGER to dry cooler
  • Single-phase: servers sit in a bath of non-conductive oil-like fluid that is pumped to a heat exchanger.
  • Two-phase: an engineered fluid boils on the chip surface and condenses on a coil above — very high heat transfer.
  • Efficiency: vendor-reported PUE as low as ~1.03–1.08, versus a global industry average of 1.56 (Uptime Institute, 2024); no server fans.
  • Water: none at the rack; heat leaves through a dry cooler.
  • Watch-outs: heavier floors, service handling, hardware warranties, and fluid chemistry — many two-phase fluids are fluorinated (PFAS / greenhouse-gas concerns).
The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
11 / 21
THE NEXT FRONTIER

Method 5 — Two-phase cold plates & microfluidics

Two-phase direct-to-chip

Refrigerant boils inside the cold plate, absorbing heat as it changes phase.

0.3
L/min per 1 kW chip
1.5
L/min for single-phase
  • Needed as GPUs pass ~1.5–2 kW TDP
  • Large-scale deployment projected 2026–2027 (IDTechEx)
  • Lower pump energy; fluid choice and handling are the open questions

In-chip microfluidics

Coolant channels etched into the back of the silicon itself — no cold plate in between.

3×
heat removal vs. cold plates
65%
lower peak silicon temperature rise
  • Microsoft + Corintis, announced Sept 2025
  • AI-optimized, leaf-vein channel patterns
  • Hotter coolant allowed → even easier dry-air heat rejection
The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
12 / 21
CLOSING THE LOOP

Method 6 — Water sourcing & heat reuse

Reclaimed water

Treated municipal wastewater replaces potable makeup. AWS: 26 sites on reclaimed water in 2025, agreements with 13 utilities covering 130 data centers. EPA's Water Reuse Action Plan supports industrial cooling reuse.

On-site treatment & recovery

High-recovery treatment (e.g., Gradiant-type systems) cycles water many more times and shrinks blowdown. Rainwater harvesting covers makeup at some sites (AWS: 14 data centers).

Heat reuse

45–55°C return water is useful heat: district heating, greenhouses, and industrial process loads. Where on-site generation exists, turbine exhaust can drive absorption chillers — cooling from waste heat, not electricity.

The trend: water becomes a backup input sourced from wastewater, and heat becomes a product instead of a waste stream.

The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
13 / 21
METHOD MATRIX

Side-by-side comparison

MethodOn-site waterRack densityEnergy effectMaturityMain tradeoff
Evaporative towerHigh · WUE 1.8+Air racksLowest energy in hot, dry climatesLegacyWater, blowdown, permitting
Adiabatic hybridPeak hours onlyAir racksSlightly higherMainstreamStill some water on hot days
Dry cooler + closed loop~0 consumedAir / RDHx+ fan & chiller energyMainstreamFootprint, noise
Direct-to-chip (warm)~0 consumed100–200 kWChillers mostly offAI standardPlumbing to every server
ImmersionNone at rack100+ kWPUE as low as ~1.03 (vendor)Niche / growingFluids, weight, serviceability
Two-phase cold plate~0 consumed1.5–2 kW+ chipsLow pump energy2026–27 rolloutRefrigerant choice
Microfluidic~0 consumedNext-gen3× heat removalR&DChip-level manufacturing
The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
14 / 21
WHAT IT COSTS

The honest tradeoff: water vs. energy

  • Evaporation is thermodynamically cheap. Replacing it with fans and chillers costs electricity: Google puts air cooling at ~10% more energy on average and roughly double on hot days.
  • Microsoft reports only a nominal annual increase by running water warmer and economizing.
  • Warm-water liquid cooling flips the equation — it removes both the tower and most chiller hours.
  • Power plants use water too. A water-free data center on a water-cooled grid still has an indirect footprint.
WHERE IT WORKS BEST

Climates where outdoor air stays cool most of the year

The colder the air, the more hours a dry cooler handles alone. That makes the Great Lakes region one of the lowest-penalty places in the U.S. to build water-free AI capacity.

The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
15 / 21
CLEVELAND APPLICATION

Applying it in Cleveland: a water-neutral stack

01
GPU racks → DLC cold plates at 45°C supply
02
Heat enters the sealed technology loop via CDUs
03
Facility loop carries heat to the roof
04
Dry coolers reject heat to outdoor air
05
Trim chillers run only on peak summer hours
06
Optional: waste heat drives absorption chillers or district heat
07
NEORSD reclaimed water for makeup only
08
AI controls balance fan, pump and chiller energy

Climate

Cold winters and moderate summers keep outdoor air below 45°C coolant temperatures year-round, so warm-water DLC can reject heat with dry coolers alone for most hours.

Water

Lake Erie proximity plus NEORSD treated effluent as a reclaimed-water backup for makeup, flushing and emergencies — no potable draw, no blowdown.

Industry

Prefabricated mechanical floors, CDU skids, risers and roof dry-cooler platforms are manufacturable locally — fits the HOLON / B-Core factory strategy.

Result: zero evaporative loss and zero potable-water demand for cooling.

The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
16 / 21
COST MODEL

Cleveland cost model: cooling CAPEX per MW

ComponentCost / MWNotes
Direct-to-chip liquid cooling$1.3M–$1.9M / MW
DLC cold plates + manifolds$0.9M–$1.3MAI racks (100–200 kW)
Pumping stations$0.25M–$0.35MN+1 redundancy
Heat-exchanger integration$0.15M–$0.25MFloor-level HX
Chiller plant (magnetic-bearing)$1.2M–$1.8M / MW
Magnetic-bearing chillers$0.8M–$1.2MOil-free
Chiller electrical + switchgear$0.25M–$0.35MMedium-voltage
Chiller plant piping$0.15M–$0.25MVertical risers
Dry coolers$0.6M–$0.9M / MW
Dry coolers$0.45M–$0.65MCleveland climate advantage
Roof structural integration$0.10M–$0.18MVertical tower design
Controls + VFD fans$0.05M–$0.10MAI-optimized
Water reuse & treatment$0.20M–$0.31M / MW
High-recovery treatment$0.12M–$0.18MGradiant-type
Reclaimed-water interface$0.05M–$0.08MNEORSD tie-in
Storage + buffer tanks$0.03M–$0.05MEmergency makeup
Modular mechanical floors$0.50M–$0.78M / MW
Prefabricated mechanical floors$0.35M–$0.55MDLC manifolds + pumps
Vertical risers$0.10M–$0.15MChilled water + power
Roof platforms$0.05M–$0.08MDry-cooler mounting
Total cooling CAPEX$3.8M–$5.7M per MW
1.301.200.600.200.50$3.80MLOW1.901.800.900.310.78$5.69MHIGHDLCChillersDry coolersWater reuseMech floors

100 MW: $380M–$570M · 300 MW: $1.14B–$1.71B. Planning-level ranges from the project cost model, not vendor quotes. Chiller line assumes a full plant; trim-only chillers with warm-water DLC would lower it.

The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
17 / 21
OPERATING COST

Cleveland cost model: annual cooling operating cost

Cooling OPEX linePer MW IT / yrBasis
Cooling electricity$68k–$102kPUE overhead 0.12–0.18 × 8,760 MWh × $65/MWh
Water (reclaimed makeup + treatment)$13k–$25kNo evaporative loss
Maintenance (DLC, chillers, dry coolers)$45k–$78kPumps, manifolds, HX, fans
Total cooling OPEX$126k–$205k per MW per year
$12.6M–$20.5M
per year · 100 MW campus
$37.9M–$61.6M
per year · 300 MW campus
HOW TO READ THIS

Electricity is the largest cooling cost — and the easiest to shrink

Every 0.01 of PUE overhead on a 100 MW campus is about $570k a year at $65/MWh. Warm-water DLC keeps chillers off most of the year, which is where Cleveland's climate pays off.

Assumes full IT load, 8,760 hours, $0.065/kWh industrial rate. Water and maintenance ranges are project planning estimates.

The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
18 / 21
FINANCIAL MODEL

10-year pro forma: 100 MW water-neutral campus

Year-1 line item$M / yrBasis
Revenue
AI hosting (wholesale)246.0100 MW × $205 / kW-month
Operating cost
Electricity, IT + cooling65.5100 MW × PUE 1.15 × 8,760 h × $0.065
Cooling water + maintenance8.1Midpoint $80.5k / MW (energy already in PUE)
Staffing + operations15.0Midpoint
Non-cooling maintenance10.0UPS, switchgear, building
Total OPEX98.5
EBITDA (year 1)$147.5M · 60% margin

CAPEX $1.12B = cooling $475M + building $320M + power $280M + land/site $45M. Escalation: revenue 1.5%, electricity 2.1%, other costs 2.0% per year. Year-10 EBITDA $162.8M; terminal value 10× EBITDA.

+$610M
Unlevered NPV @ 8.5%
15.8%
Unlevered IRR
26.5%
Levered equity IRR · 60% debt @ 5.2%, 20-yr
$92.6M
Year-1 equity cash flow after $54.8M debt service
NOT YET IN THE MODEL

Income and property taxes · GPU / equipment refresh · lease-up ramp and vacancy · insurance. Each lowers these returns; add them before investor use. Revenue rate and power price are planning assumptions, not quotes.

The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
19 / 21
WHAT THIS MEANS

Takeaways

For the industry

  • Evaporative towers are being designed out of new AI capacity.
  • Warm-water direct-to-chip + dry coolers is the new baseline; immersion, two-phase and microfluidics follow as chips get hotter.
  • Water becomes a backup input from reclaimed sources; heat becomes a product.

For Cleveland

  • Climate makes water-free cooling cheaper here than in the Sun Belt.
  • A zero-evaporation commitment answers the first question every neighborhood will ask.
  • The mechanical stack — CDUs, manifolds, dry coolers, prefabricated floors — is a local manufacturing opportunity.
  • Next step: add taxes, equipment refresh and lease-up to the pro forma before investor use.
The FixOurStreets216 Project
FOS216-NMW-001 · REV B · 2026-09-25
20 / 21
REFERENCES

Sources

  1. Microsoft Cloud Blog, “Sustainable by design: Next-generation datacenters consume zero water for cooling,” Dec 9, 2024 — microsoft.com
  2. Microsoft Source, “AI chips are getting hotter. A microfluidics breakthrough goes straight to the silicon,” Sept 24, 2025 — news.microsoft.com
  3. Android Headlines / Tom's Hardware, Microsoft Fairwater “restaurant-level” water claim, June 2026
  4. DatacenterDynamics, “AWS in-row heat exchanger to reduce water use…” — AWS 2025 WUE 0.12 L/kWh, PUE 1.14, reclaimed-water program
  5. Axios, “Google pushes water standards amid data center backlash,” June 3, 2026
  6. Meta Data Centers, “Water” — datacenters.atmeta.com/water
  7. NVIDIA Blog, “Hotter Than a Hot Tub: The 45°C Breakthrough to Cool AI's Biggest Machines,” June 22, 2026
  8. IDTechEx, “Two-Phase Cold Plate Cooling Will Take Off as Early as 2026–2027”
  9. Uptime Institute, Global Data Center Survey 2024 — average PUE 1.56
  10. Lawrence Berkeley National Laboratory, 2024 United States Data Center Energy Usage Report (Dec 2024), as summarized by RPM Water Equity Solutions
  11. Project folder No-More-Water: “Water is history.docx,” “10-year-proforma.docx,” “10-year-proforma-waste heat-onsite-power.docx,” component-cost-per-mw-3 through -7.csv

Company figures are self-reported. Cost ranges are planning-level estimates for discussion, not vendor quotes. FOR DISCUSSION — NOT FOR CONSTRUCTION.